Schneider Electric TeSys D kontaktor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 25 A - 230 V AC kalem; LC1D128P7
Contactor, TeSys Deca, 4P(2NO+2NC), AC-1, 0 to 440V, 25A, 230VAC 50/60Hz coil; LC1D128P7...
VAT-exclusive price: 9.196,00 |
VAT-inclusive price: 11.035,20 |
Contactor, TeSys Deca, 4P(2NO+2NC), AC-1, 0 to 440V, 25A, 230VAC 50/60Hz coil; LC1D128P7
Range of product | TeSys Deca |
---|---|
Product or component type | Contactor |
Device short name | LC1D |
Contactor application | Resistive load |
Utilisation category |
AC-1 AC-3 AC-3e AC-4 |
Poles description | 4P |
[Ue] rated operational voltage |
Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC |
[Ie] rated operational current | 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
[Uc] control circuit voltage | 230 V AC 50/60 Hz |
Compatibility code | LC1D |
---|---|
Pole contact composition | 2 NO + 2 NC |
Contact compatibility | M6 |
Protective cover | With |
[Ith] conventional free air thermal current |
25 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit |
Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current |
105 A 40 °C - 10 s for power circuit 210 A 40 °C - 1 s for power circuit 30 A 40 °C - 10 min for power circuit 61 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
Associated fuse rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1 40 A gG at <= 690 V coordination type 1 for power circuit 25 A gG at <= 690 V coordination type 2 for power circuit |
Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
Power dissipation per pole | 1.56 W AC-1 |
[Ui] rated insulation voltage |
Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
Overvoltage category | III |
Pollution degree | 3 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
Safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Mechanical durability | 15 Mcycles |
Electrical durability | 0.8 Mcycles 25 A AC-1 at Ue <= 440 V |
Control circuit type | AC at 50/60 Hz |
Coil technology | Without built-in suppressor module |
Control circuit voltage limits |
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
Inrush power in VA |
70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
Hold-in power consumption in VA |
7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
Heat dissipation | 2…3 W at 50/60 Hz |
Operating time |
12...22 ms closing 4...19 ms opening |
Maximum operating rate | 3600 cyc/h 60 °C |
Connections - terminals |
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end |
Tightening torque |
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Auxiliary contact composition | 1 NO + 1 NC |
Auxiliary contacts type |
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
Signalling circuit frequency | 25...400 Hz |
Minimum switching voltage | 17 V for signalling circuit |
Minimum switching current | 5 mA for signalling circuit |
Insulation resistance | > 10 MOhm for signalling circuit |
Non-overlap time |
1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
Mounting support |
Rail Plate |
Standards |
CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 IEC 60335-1 |
---|---|
Product certifications |
RINA GOST CSA UL LROS (Lloyds register of shipping) DNV CCC GL BV UKCA |
IP degree of protection | IP20 front face conforming to IEC 60529 |
Protective treatment | TH conforming to IEC 60068-2-30 |
Climatic withstand |
conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
Permissible ambient air temperature around the device |
-40…60 °C 60…70 °C with derating |
Operating altitude | 0...3000 m |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Flame retardance | V1 conforming to UL 94 |
Mechanical robustness |
Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor open (10 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms) |
Height | 85 mm |
Width | 45 mm |
Depth | 92 mm |
Net weight | 0.365 kg |
Similar products:
Schneider Electric TeSys D kontaktor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 230 V AC kalem ; LC1D25P7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 230 V AC coil
-

(Out of stock)
8.060,00
Schneider Electric TeSys D kontaktor - 4P(4 NO) - AC-1 - <= 440 V 40 A - 230 V AC 50/60 Hz kalem; LC1DT40P7
TeSys D kontaktor - 4P(4 NO) - AC-1 - <= 440 V 40 A - 230 V AC 50/60 Hz kalem
-

(Out of stock)
16.150,00
Schneider Electric TeSys D kontaktor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 40 A - 230 V AC kalem
Schneider Electric - TeSys D kontaktor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 40 A - 230 V AC kalem
-

(Out of stock)
Price on request
Schneider Electric TeSys D kontaktor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 40 A - 24 V AC kalem; LC1D258B7
Contactor, TeSys Deca, 4P(2NO+2NC), AC-1, <= 440V, 40A, 24V AC 50/60Hz coil, screw terminal; LC1D258B7
-

(Out of stock)
18.206,00
Schneider Electric TeSys D sistem izmene nap.kontaktor-4P(4 NO)-AC-1 - <= 440 V 25 A -230 VAC kalem;LC2DT25P7
TeSys D changeover contactor - 4P(4 NO) - AC-1 - <= 440 V 25 A - 230 V AC coil
-

(Out of stock)
19.989,00
Schneider Electric TeSys D kontaktor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 60 A 230 V AC 50/60 Hz kalem
Schneider Electric - TeSys D kontaktor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 60 A 230 V AC 50/60 Hz kalem
-

(Out of stock)
Price on request